Sample answer · Ohio · Propane
You likely must file.
How the amount was worked out
- Density: specific gravity 0.51 × 8.34 lb per gal of water
- 4.25 lb per gal
- 3,000 gal × 4.25 lb per gal
- 12,750 lb
Source: Williams propane safety data sheet, revision July 26, 2024 · checked
Source: EPA: Tier II Forms, Regulatory Overview and Instructions, May 2026 · checked
Thresholds it was set against
- Federal threshold, hazardous chemical
- 10,000 lb
-
12,750 lb is at or over it.
Source: 40 CFR 370.10(a)(2)(i) · checked
Next steps in Ohio
- File through
- EPA Tier2 Submit file emailed to the state with a certification letter Email SERC@epa.ohio.gov
- Due
- March 1 for the report; fee by March 31
- Fee
- $150 base, plus $20 per hazardous chemical, plus $150 per extremely hazardous substance; capped at $2,500 per facility. Oil and gas extraction storage: $50 flat for up to 25 facilities. Payment: Check or money order to Treasurer, State of Ohio, mailed with the invoice stub. No online payment mentioned
- Copies for local agencies
- File and letter to the state and the county committee; a paper copy with the map to the fire department
- Also asked for
- Facility map required; certification letter; D-U-N-S; recommended file name; Ohio Facility Identification Form
- Worth knowing
- 10% late fee on payments postmarked after March 31. New chemical: notice in 90 days (60 for an extremely hazardous substance)
- What the state's own pages describe
- reporting year 2025
Source: Ohio: SERC manual · checked